Earthing Systems
TN-S, TN-C-S (PME) and TT systems.
TN-S
Separate neutral and earth back to the source, usually via cable sheath. Typical max Ze 0.8 Ω.
TN-C-S (PME)
Combined PEN conductor in the supply; separated at the origin. Typical max Ze 0.35 Ω. Restrictions apply for EV charging and outdoor equipment (722.411.4).
TT
Installation earth electrode. RCD needed for fault protection; RA × IΔn ≤ 50 V. Electrode resistance above 200 Ω may be unstable.
Key regulations
312.2411.4411.5542