Theory

CB

Circuit Breaker (MCB)

BS EN 60898 devices with thermal (overload) and magnetic (short-circuit) trips.

Types

Type B trips instantaneously at 3–5 × In (domestic). Type C at 5–10 × In (inductive loads). Type D at 10–20 × In (high inrush).

Selection

Choose In ≥ Ib and ≤ Iz. Check the maximum Zs from Table 41.3 so the device disconnects within 0.4 s on final circuits up to 63 A (TN).

Key regulations

411.3.2Table 41.3533